| A'a. | Abu | Sigar yau da kullun dabi'u | Darajar garanti |
| 1 | Ƙarfin wutar lantarki mai mitoci gwaji | 4.5Uo, minti 5 | 117kV, mintuna 5, Babu ɗayan samfuran da aka haɗa da suka karye ƙasa ko walƙiya |
| 2 | Gwajin fitar da wani ɓangare (zafin ɗaki, gwaji (sama da 5pC) | 1.73Uo <5Pc | Kasa da 45kV, ƙarfin fitarwa na kowane haɗuwa samfurin shine ≤2pC |
| 3 | Nauyin matsin lamba mai ɗorewa gwajin zagayowar | Dangane da GB/T 12706.4 | A cikin ƙarfin lantarki na mitar wutar lantarki 65kv da waya mai dumama zuwa zafin jiki na 95℃ ~ 100℃, kammala zagaye uku mara kyau, babu walƙiya, a'a rushewa |
| 4 | Gwajin fitar da wani ɓangare (zafin jiki mai yawa) | 1.73Uo <5Pc | Lokacin da zafin jiki na mai gudanarwa shine 95℃ -100℃ kuma a 45kV, adadin fitarwa na kowane rukuni na samfurori is≤2 pC |
| 5 | Gwajin ƙarfin lantarki na impulse (a zafin jiki mai gudanarwa daga 95℃ zuwa 100℃) | ±200kV, sau 10 kowanne | Lokacin da zafin wutar lantarki ya kasance tsakanin 95 ℃ da 100℃, a 200kV, polarity mai kyau da mara kyau sun kasance An gwada sau 10 kowannensu, kuma babu ɗayan samfuran da aka haɗa an huda su ko kuma an cire su |
| 6 | Ƙarfin wutar lantarki na mitar wutar lantarki gwaji bayan tasiri | 2.5Uo, minti 15 | 65kV, minti 15, Babu ɗayan samfuran da aka haɗa da suka karyeƙasa ko walƙiya |
| 7 | Gwajin kwanciyar hankali na zafi | Dangane da GB/T 12706.4 | 24.2kA,2.02s&24.1kA,2.01s Babu wani abu da aka gani lalacewa bayan gajerun da'irori biyu |
| 8 | Gwajin kwanciyar hankali mai ƙarfi | Dangane da GB/T 12706.4 | 84.9kA,0.06s, Lalacewa mara ganuwa |
| 9 | Gwajin danshi | 1.25 Uo, 300h | Bayan 32.5 KV da sa'o'i 300, babu ɗaya daga cikin samfuran da aka haɗaya lalace ko kuma ya ɓace, kuma babu wata babbar illa da ta faru |
| 10 | Gajeren da aka yarda da shi- ƙarfin da'ira na abin da aka haɗa | (An cike ta da ƙungiyar aikin) | Ba ƙasa da kebul ɗin da aka zaɓa ba |
| 11 | Matsakaicin zafin da aka yarda da shi na kayan haɗi a lokacin aiki na yau da kullun | (An cike ta da ƙungiyar aikin) | 90℃ |
| 12 | Matsakaicin da aka yarda yanayin zafi lokacin da gajerun hanyoyin haɗi | (An cike ta da ƙungiyar aikin) | 250℃ |